Yokogawa UT35A Temperature Controller that we are offering is a precision device designed to control a heater or other equipment by comparing a sensor signal with a set point. Owing to its superior design and reliable performance, it is preferred by our customers. Yokogawa UT35A Temperature Controller is easy to install and maintain. It does not degrade in quality or become inferior in the long run. Our customers can approach us to purchase the controller at a budget-friendly price.
Specifications :
Universal Input (Equipped as standard)
Number of inputs: 1
Input type, instrument range, and measurement accuracy: See the table below,
Input Type | Instrument Range | Accuracy | ||
| C | F | | |
Thermocouple | K | -270.0 to 1370.0 C | 450.0 to 2500.0F | 0.1% of instrument range 1 digit for 0C or more 0.2% of instrument range 1 digit for less than 0C 2% of instrument range 1 digit for less than -200.0C of thermocouple |
-270.0 to 1000.0 C | -450.0 to 2300.0 F | |||
-200.0 to 500.0 C | -200.0 to 1000.0 F | |||
J | -200.0 to 1200.0 C | -300.0 to 2300.0 F | ||
T | -270.0 to 400.0 C | -450.0 to 750.0 F | ||
0.0 to 400.0 C | -200.0 to 750.0 F | |||
B | 0.0 to 1800.0 C | 32 to 3300 F | 0.15% of instrument range 1 digit for 400C or more | |
S | 0.0 to 1700.0 C | 32 to 3100 F | 0.15% of instrument range 1 digit | |
R | 0.0 to 1700.0 C | 32 to 3100 F | ||
N | -200.0 to 1300.0 C | -300.0 to 2400.0 F | 0.1% of instrument range 1 digit | |
E | -270.0 to 1000.0 C | -450.0 to 1800.0 F | 0.1% of instrument range 1 digit for 0C or more 0.2% of instrument range 1 digit for less than 0C 1.5% of instrument range 1 digit for less than -200.0C of thermocouple E. | |
L | -200.0 to 900.0 C | -300.0 to 1600.0 F | ||
U | -200.0 to 400.0 C | -300.0 to 750.0 F | ||
0.0 to 400.0 C | -200.0 to 1000.0 F | |||
W | 0.0 to 2300.0 C | 32 to 4200 F | 0.2% of instrument range 1 digit (Note 2) | |
Platinel 2 | 0.0 to 1390.0 C | 32.0 to 2500.0 F | 0.1% of instrument range 1 digit | |
PR20-40 | 0.0 to 1900.0 C | 32 to 3400 F | 0.5% of instrument range 1 digit for 800 C or more | |
W97Re3-W75Re25 | 0.0 to 2000.0 C | 32 to 3600 F | 0.2% of instrument range 1 digit | |
JPt100 | -200.0 to 500.0C | -300.0 to 1000.0F | 0.1% of instrument range 1 digit (Note 1) | |
-150.00 to 150.00C | -200.0 to 300.0 F | 0.1% of instrument range 1 digit | ||
Pt100 | -200.0 to 850.0C - | 300.0 to 1560.0 F | 0.1% of instrument range 1 digit (Note 1) | |
-200.0 to 500.0C | -300.0 to 1000.0F | |||
-150.00 to 150.00C | -200.0 to 300.0F | 0.1% of instrument range 1 digit | ||
Standard signal | 0.400 to 2.000 V | 0.1% of instrument range 1 digit | ||
1.000 to 5.000 V | ||||
4.00 to 20.00 mA | ||||
DC voltage/current | 0.000 to 2.000 V | |||
0.00 to 10.00 V | ||||
0.00 to 20.00 mA | ||||
-10.00 to 20.00 mV | ||||
0.0 to 100.0 mV |
The accuracy is that in the standard operating conditions: 23 2 C, 55 10%RH, and power frequency at 50/60 Hz.
Note 1: 0.3 C 1 digit in the range between 0 and 100 C, 0.5C 1 digit in the range between -100 and 200C.
Note 2: W: W-5% Re/W-26% Re(Hoskins Mfg.Co.). ASTM E988
Contact Input Specifications:
Analog Output Specifications :
Retransmission Output Specifications :
15 V DC Loop Power Supply Specifications :
Step Response Time Specifications :
Relay Contact Output Specifications :
Transistor Contact Output Specifications :
Position Proportional Output Specifications :
Heater Break Alarm Specifications :
24 V DC Loop Power Supply Specifications :