We are instrumental in supplying the top-of-the-line Fuji Pid Temperature Controller that is popularly known among our customers owing to its superior design and performance. This device is easy to use and maintain. Having the capability of enduring heat, chemical attacks, and tough conditions, this Fuji Pid Temperature Controller is sure to last for an extended period of time. Our customers can approach us to purchase the temperature controller at a budget-friendly price.
Salient Features :
Specifications :
General | |
Power supply voltage | 100 V (-15%) to 240 V (+10%) AC, 50/60 Hz, or 24 V (10%) AC/DC |
Power consumption | Model 100 to 240 V AC 24 V DC/AC |
PXF4 10 VA MAX. 5 VA MAX. | |
PXF5 & PXF9 13 VA MAX. 8 VA MAX. | |
Insulation resistance | 20 M (at 500 V DC) |
Withstand voltage | Between the power source and other terminals: 1500 V AC for 1 min |
Between the relay output and other terminals: 1500 V AC for 1 min Others: 500 V AC for 1 min | |
Input impedance | Thermocouple, mV input: 1 M |
Current input: 150 (built-in diode) | |
Voltage input: About 1 M | |
Allowable input voltage | DC voltage input: 35 V |
Current input: 25 mA | |
Thermocouple, RTD, mV input: 5 V | |
Effect of signal source resistance | Thermocouple, mV input: 0.3%FS 1 digit per 100 |
Voltage input: 0.3%FS 1 digit per 500 | |
Allowable wire resistance | RTD: 10 per wire |
Input value correction | (a) User adjustment: 50%FS for each of zero and span point |
(b) Process value shift: 10%FS | |
(c) Input filter: 0.0 to 120.0 s (filter is off when set to 0.0) | |
(d) Square root extraction: -0.1 to 105% (OFF if set to -0.1%) | |
Noise reduction ratio | Normal mode: 40 dB (50/60 Hz) |
Common mode: 120 dB (50/60 Hz) | |
Between input and power supply: 1 C at 220 V AC, 50/60 Hz | |
Temperature effect on sensitivity | 0.3%FS per 10 C |
Display and keys | |
Type | Backlit LCD |
Keys | 5 embossed keys |
Cotents | PV: 11-segment, 4-digit white |
SV: 11-segment, 4-digit green | |
Parameter name: 7-segment, 4-digit orange | |
Status indicator: 42 | |
Luminance setting | 4 levels |
User key | Allows you to switch between: auto/manual, standby on/off, remote SV, ramp/soak, etc. |
Structure | |
Installation | Panel mounting |
Electrical connection | M3 screw terminal |
Case | Material: ABS, PPO |
| Non-combustibility grade: UL94V-0 equivalent |
| Color: black |
IP rating | Panel front side: IP66, NEMA-4X equivalent (When the panel is mounted using our genuine packing. Not water-proof if mounted closely together.) |
Body: IP20 equivalent (slits on top and bottom) | |
Terminals: IP00 equivalent | |
Weight | PXF4: approx. 100 g, PXF5: approx. 170 g, PXF9: approx. 220 g |
PV input | |
No. of inputs | 1 |
Signal | Thermocouples, RTD, voltage, or current |
| See a separate table for measurement range. |
Input setting | Programmable scale |
Sampling rate | 50 ms |
Indication accuracy (at 23C) | Thermocouple input: either 1C 1 digit or 0.3% of indicated value 1 digit, whichever is larger |
except: | |
Thermocouple B: 0 to 400 C: no accuracy assurance | |
Thermocouple R: 0 to 500C: 3 C 1 digit | |
Thermocouples of which measuring range is between -200C and -100C: 2 C 1 digit | |
RTD input: 0.8 C 1 digit or 0.2% of indication value 1 digit, whichever is larger | |
mV input, voltage input, current input: 0.3%FS 1 digit | |
Over range under range | Out of the range between -5% and 105% FS (accuracy is not assured between -5 and 0, and between 100 and 105%FS) |
Remote SV input (option) | |
No. of inputs | 1 |
Signal | Voltage: 0-5 V DC, 1-5 V DC, 0-10 V DC |
| Current (250 resistor is required): 0-20 mA DC, 4-20 mA DC |
Impedance Approx. | 1 M |
Sampling rate | 50 ms |
Current transformer input (option) | |
Input type | Single phase CT, 1 point |
For 1 A to 30 A: CTL-6-S-H | |
For 20 A to 100 A: CTL-12-S36-8 | |
Detection range | 1 A to 100A |
Accuracy | Setpoint 5%FS |
Resolution | 0.1A |
ON time necessary for detection | 300 ms |
Digital input (option) | |
No. of inputs | PXF5 and PXF9: up to 3 |
PXF4 standard version: 1 | |
PXF4 motorized valve control version: 3 | |
Switch | Volt-free contact or transistor |
Contact capacity | 5 V DC, about 2 mA (per point) |
Input judgment | ON voltage: 2 V DC or lower |
| OFF voltage: 3 V DC or higher |
Input pulse width | 50 ms |
Functions | Remote mode selection, SV changeover, control standby, AT startup, timer startup, alarm unlatch, program selection, start/stop/ reset, PID switching (normal/reverse), etc. |
Valve position feedback signal input (option for PXF5 and PXF9 only) | |
Resistance range | 100 to 2.5k, three-wire |
Resolution | 0.5% FS |
Accuracy | 1.0%FS |
Temperature effect on sensitivity | 0.5%FS per 10C |
Burnout function | None |
Alarm output (option) | |
No. of points | Relay contact |
Shared COM: PXF4: 3, PXF5 & PXF9: 5 | |
Independent COM: PXF4: 2, PXF5 & PXF9: 3 | |
Contact | Contact structure: SPST-NO |
Contact capacity: 250 V AC / 30 V DC, 1A (resistive load) | |
Minimum ON/OFF current: 10 mA (5 V DC) | |
Mechanical life: 20 million operations (100 operations/min) | |
Electrical life: 100,000 operations (rated load) | |
Functions | Alarm output, main unit control mode output, program status output, control output 1 and 2, etc. |
Output cycle | 100 ms |
Alarm | |
No. of alarms | PXF4: 3 |
| PXF5 & PXF9: 5 (depends on the number of DO) |
Alarm type | Process value (upper limit/lower limit, absolute/deviation, range), device error, etc.(non-excitation, delay, latch, timer function available) |
Heater current alarm function (option) | Current transformer (CT) is to be prepared separately |
Detectable range: 1 A to 100 A | |
Detected current resolution: 0.1A | |
Setting resolution: 0.1A | |
Hysteresis: 0.0 to 100.0 A | |
Transfer output (option) | |
No. of points | 1 |
Type | 0-20 mA DC / 4-20 mA DC / 0-5 V DC / 1-5 V DC / 0-10 V DC / 2-10 V DC |
Guaranteed output range: 0-21 mA DC / 0-10.5 V DC | |
Accuracy: 0.2%FS (5%FS at 1 mA or smaller) | |
Resolution: 10,000 | |
Load resistance: 500 (current), 10 k (voltage) | |
Output cycle | 100 ms |
Contents | PV, SV, DV, MV |
Additional function | Scaling function |